2005-06-08 00:00:00 | DENIED | | | | 1) SPECIFY THE MEAN ROOF HEIGHT OF THE | | STRUCTURE ON THE APPLICATION. | | | | 2) THE DESIGN PRESSURES FOR THE APPROVED | | SYSTEMS THAT WERE SUBMITED WILL NOT MEET | | THE REQUIRED PRESSURES. ON A BUILDING UP | | TO 30 FEET IN HEIGHT WITH A BASIC WIND | | SPEED OF 140 MPH, THE REQUIRED DESIGN | | PRESSURE FOR A FLAT ROOF IN ZONE 3 IS | | -89 PSF. SEE FBC TABLE 1606.2B. | | | | IF YOU HAVE QUESTIONS CALL: | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 |
|