Plan Review Notes For Permit 05060474 |
Permit Number |
05060474 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-09-22 00:00:00 | BUILDING SUBMITTAL CHECKLIST: | | 1- | | BUILDING SUBMITTAL CHECKLIST: | | 1- ACCORDING TO ROBIN FROM KENCO COMM. | | ENERGY CALCS WILL BE REVISED AGAIN TO | | HOUSE SPECIFIC ORIENTATION. RE-SUBMIT | | REVISED ENERGY CALCS. | | | | 2- NEED TO APPLY FOR SHUTTERS PERMIT. | | | | 3- NEED TO REVISE ROOF FRAMING PLAN BY | | ENTRY PORCH ROOF. CONCRETE BEAM DOESN'T | | EXTEND ALL THE WAY TO THE FOYER AREA. | | ALSO, KNEEWALL IS NOT CONCRETE EITHER. | | REVISE AS REQUIRED AND SPECIFY | | CORRESPONDING TRUSS ANCHOR. SEC. | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. | | | | 4- TRUSS ANCHOR SCHEDULE: REVISE # OF | | NAILS FOR HUS26. SEE 2005 CATALOGUE. | | | | 5- WINDOW MULLION SPECIFIED FOR FIXED | | WINDOWS AT GREAT ROOM DOESN'T RESIST THE | | DESIGN PRESSURES. RE-REVISE AS REQUIRED. | | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. | | | | 6- PROVIDE PRODUCT APPROVAL FOR: | | A) 1 HR FIRE RATED ATRIUM DOOR WITH | | INSWING AS SHOWN ON PLANS. | | | | B) WINDOW MULLION SPECIFIED FOR FIXED | | WINDOWS AT GREAT ROOM | | | | ***NOTE: REVISION FEES WILL BE APPLIED. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|