Plan Review Notes For Permit 05060474 |
Permit Number |
05060474 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-07-18 00:00:00 | BUILDING REVIEW PROVISO: | | | | 1- REVISE ENERGY CALCULATIONS FOR WORST | | CASE SCENARIO FOR THIS MODEL. | | 2- SHUTTERS UNDER A SEPARATE PERMIT. | | 3- ROOF FRAMING PLAN: REVISE CONNECTOR | | SPECIFIED AT FRONT PORCH. SEE DETAILS 4 | | AND 5 OF SHEET D-1. | | 4- TRUSS ANCHOR SCHEDULE: REVISE NAIL | | SIZE FOR HUS26. SEE CATALOGUE. | | 5- SPECIFY SIZE AND ANCHORS FOR LARGE | | FIXED WINDOW AT GREAT ROOM. SEC. | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. | | 6- PROVIDE FLORIDA OR LOCAL PRODUCT | | APPROVAL FOR: | | A) 1 HR FIRE RATED DOOR AT ATRIUM. | | B) FIXED WINDOWS. | | C) SINGLE HUNG WINDOWS. | | D) ROOF TILE. | | E) WINDOW MULLION AT GREAT ROOM WINDOWS. | | 7- CLARIFY WINDOW DOOR SCHEDULES | | ICLUDING SIMBOLS USED ON PLAN. |
|