Plan Review Notes
Plan Review Notes For Permit 05060468
Permit Number 05060468
Review Stop E
Sequence Number 2
Notes
Date Text
2006-02-10 00:00:00REDLINED:
  
  
 250.52A5 GRND ROD SHALL BE A MIN OF 8'
  
 VIF OCP FOR CU, SHOWS 9.8KW ON 40A OCP


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved