Plan Review Notes For Permit 05060468 |
Permit Number |
05060468 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-09-22 00:00:00 | BUILDING SUBMITTAL CHECKLIST: | | 1- ACCORDING TO ROBIN FROM KENCO COMM. | | ENERGY CALCS WILL BE REVISED AGAIN TO | | SPECIFIC HOUSE ORIENTATION. RE-SUBMIT | | RE-REVISED ENERGY CALCS. | | | | 2- NEED TO APPLY FOR SHUTTERS PERMIT. | | | | 3- NEED TO REVISE ROOF FRAMING PLAN BY | | ENTRY PORCH ROOF. CONCRETE BEAM DOESN'T | | EXTEND ALL THE WAY TO THE FOYER AREA. | | ALSO, KNEEWALL DOESN'T HAVE CONCRETE | | BEAM. REVISE AS REQUIRED AND SPECIFY | | CORRESPONDING TRUSS CONNECTOR. SEC. | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001 | | | | 4- TRUSS ANCHOR SCHEDULE: REVISE # OF | | NAILS SPECIFIED FOR HUS26. SEE 2005 | | CATALOGUE. | | | | 5- WINDOW MULLION SIZE SPECIFIED FOR | | FIXED WINDOWS AT GREAT ROOM DOESN'T | | RESIST THE DESIGN PRESSURES. REVISE SIZE | | OF MULLION AS REQUIRED. SEC. 104.2.1.2 | | CITY AMENDMENTS TO FBC 2001. | | | | 6- PROVIDE PRODUCT APPROVAL FOR: | | A) 1HR FIRE RATED INSWING DOOR AS SHOWN | | IN PLANS BY ATRIUM AREA. | | | | B) WINDOW MULLION SIZE AT GREAT ROOM | | FIXED WINDOWS SPECIFIED IN RE-REVISED | | ITEM #5 ABOVE. | | | | ***NOTE: REVISION FEES WILL APPLY. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER. | | (561)805-6712 |
|