Plan Review Notes For Permit 05060468 |
Permit Number |
05060468 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-07-19 00:00:00 | BUILDING REVIEW PROVISO: | | 1- NEED WORST CASE SCENARIO ENERGY CALCS | | 2- SHUTTERS UNDER A SEPARATE PERMIT. | | 3- ROOF FRAMING PLAN: REVISE CONNECTOR | | SPECIFIED AT FRONT PORCH. SEE DETAILS | | 4/D1 AND 5/D1. | | 4- REVISE NAIL SIZE FOR HUS26 CONNECTOR. | | 5- SPECIFY SIZE AND ANCHORS FOR LARGE | | FIXED WINDOWS AT GREAT ROOM AREA. | | 6- RE-SUBMIT PRODUCT APPROVAL FOR: | | A) 1 HR FIRE RATED ATRIUM DOOR ASSEMBLY. | | B) FIXED WINDOWS. | | C) SINGLE HUNG WINDOWS. | | D) ROOF TILE. | | E) LARGE WINDOW MULLION FOR LARGE FIXED | | WINDOWS AT GREAT ROOM. | | 7- PROVIDE CLEAR DOOR AND WINDOW | | SCHEDULE. SYMBOLS USED FOR DOORS AND | | WINDOWS ARE MIXED TOGETHER. |
|