2006-02-03 00:00:00 | ********* UNSAT ********* | | | | 1)NOTE: PLEASE SEE OCP HAS NOW BEEN | | INCREASED FOR PANEL "B" TO 125A'S, | | HOWEVER PLEASE SEE RISER HAS NOT | | INCREASED PANEL ORFEEDERS AND PANEL | | SCHEDULE ALSO SHOWS 100A. | | PLEASE CORRELATE , UPGRADE PANEL, | | FEEDERS ETC. | | | | 240.4,310.15B6, 215.5 ETC. | | | | | | 2)NOTE: PLEASE SEE MIN GRND ROD 8' PER | | 250.52A5 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE IN CONTACTING | | THIS OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|