Plan Review Notes
Plan Review Notes For Permit 05060465
Permit Number 05060465
Review Stop E
Sequence Number 2
Notes
Date Text
2006-02-03 00:00:00********* UNSAT *********
  
 1)NOTE: PLEASE SEE OCP HAS NOW BEEN
 INCREASED FOR PANEL "B" TO 125A'S,
 HOWEVER PLEASE SEE RISER HAS NOT
 INCREASED PANEL ORFEEDERS AND PANEL
 SCHEDULE ALSO SHOWS 100A.
 PLEASE CORRELATE , UPGRADE PANEL,
 FEEDERS ETC.
  
 240.4,310.15B6, 215.5 ETC.
  
  
 2)NOTE: PLEASE SEE MIN GRND ROD 8' PER
 250.52A5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  