Plan Review Notes For Permit 05060465 |
Permit Number |
05060465 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-09-22 00:00:00 | BUILDING SUBMITTAL CHECKLIST: | | 1- ACCORDING TO ROBIN FROM KENCO | | COMMUNITIES ENERGY CALCS WILL BE | | RE-REVISED AGAIN TO HOUSE SPECIFIC | | ORIENTATION. RE-RESUBMIT REVISE ENERGY | | CALCULATIONS. | | | | 2- NEED TO APPLY FOR SHUTTERS PERMIT. | | | | 3- REVISE ROOF FRAMING PLAN BY THE ENTRY | | PORCH ROOF. CONCRETE BEAM DOESN'T EXTEND | | TO THE FOYER AREA. ALSO, THERE IS NOT | | CONCRETE BEAM BY KNEEWALL SIDE. SEE | | PLANS. REVISE AS REQUIRED AND SPECIFY | | CORRESPONDING TRUSS CONNECTORS. SEC. | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. | | | | 4- TRUSS ANCHOR SCHEDULE; REVISE NUMBER | | OF NAILS FOR HUS26. SEE 2005 CATALOGUE. | | | | 5- WINDOW MULLION SPECIFIED FOR FIXED | | WINDOWS IN GREAT ROOM DOESN'T RESIST THE | | DESIGN PRESSURES. REVISE AS REQUIRED. | | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. | | | | 6- PROVIDE PRODUCT APPROVAL FOR: | | A) 1 HR FIRE RATED INSWING DOOR AS SHOWN | | ON PLANS. | | | | B) RE-REVISED WINDOW MULLION SPECIFIED | | FOR FIXED WINDOWS IN GREAT ROOM AREA. | | | | ***NOTE: REVISION FEES WILL BE APPLIED. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|