Plan Review Notes For Permit 05060463 |
Permit Number |
05060463 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-09-22 00:00:00 | BUILDING SUBMITTAL CHECKLIST: | | 1- ACCORDING TO ROBIN FROM KENCO | | COMMUNITIES THE ENERGY CALCS WILL BE | | RE-REVISED AGAIN TO HOUSE SPECIFIC | | ORIENTATION. RE-RESUBMIT ENERGY CALCS. | | | | 2- REVISE ROOF FRAMING PLAN BY THE ENTRY | | PORCH AREA. CONCRETE BEAM DOESN'T EXTEND | | BACK TO THE FOYER AREA. ALSO, THERE IS | | NOT CONCRETE BEAM BY KNEEWALL AREA. | | REVISE AND SPECIFY CORRESPONDING TRUSS | | CONECTORS. SEC. 104.2.1.2 CITY | | AMENDMENTS TO FBC 2001. | | | | 3- TRUSS ANCHOR SCHEDULE: REVISE # OF | | NAILS FOR HUS26. SEE 2005 CATALOGUE. | | | | 4- WINDOW MULLION SPECIFIED FOR FIXED | | WINDOWS DOESN'T RESIST THE DESIGN | | PRESSURES. RE-REVISED AS REQUIRED AND | | SPECIFY CORRESPONDING CONNECTORS. | | | | 5- PROVIDE PRODUCT APPROVAL FOR: | | A) 1HR FIRE RATED INSWING DOOR AS SHOWN | | ON PLANS. | | | | B) RE-REVISED WINDOW MULLION SIZE | | SPECIFIED FOR GREAT ROOM. | | | | ***NOTE: REVISION FEES WILL APPLY. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712. |
|