Plan Review Notes For Permit 05060463 |
Permit Number |
05060463 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-07-01 00:00:00 | BUILDING REVIEW PROVISO: | | 1- PROVIDE THE REVISED ENERGY | | CALCULATIONS FOR WORST CASE SCENARIO. | | 2- SHUTTERS UNDER A SEPARATE PERMIT. | | 3- ROOF FRAMING PLAN: REVISE CONNECTOR | | SPECIFIED AT FRONT PORCH MASONRY BEAMS. | | NEED MASONRY CONNECTOR. SEE DETAILS 4/D1 | | AND 5/D1 AND REVISE AS REQUIRED. | | 4- TRUSS ANCHOR SCHEDULE: REVISE NAIL | | SIZE FOR HUS26. SEE CATALOGUE. | | 5- PROVIDE PRODUCT APPROVAL FOR: | | A) 1 HR FIRE RATED DOOR & EGRESS | | ASSEMBLY. | | B) FIXED WINDOWS NEED FLORIDA PRODUCT | | APPROVAL COVER PAGE. | | C) SINGLE HUNG WINDOWS NEED FLORIDA | | PRODUCT APPROVAL COVER PAGE. | | D) ROOF TILE NEEDS MATCHING FLORIDA | | PRODUCT APPROVAL. | | E) WINDOW MULLIONS FOR FIXED WINDOWS: | | CLEARLY SPECIFY SIZE OF MULLION AND | | ANCHOR TO BE USED AT GREAT ROOM FIXED | | WINDOW TO MEET THE DESIGN PRESSURES | | CALCULATED ON PLANS. SEC. 104.2.1.2 CITY | | AMENDMENTS TO FBC 2001. | | 6- PROVIDE CLEAR WINDOW & DOOR SCHEDULES | | WITH SIZES MATCHING PLANS. SYMBOLS TO | | MATCH ALSO. |
|