Plan Review Notes For Permit 05060459 |
Permit Number |
05060459 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-09-22 00:00:00 | BUILDING SUBMITTAL CHECKLIST: | | 1- ACCORDING TO ROBIN FROM KENCO | | COMMUNITIES THE ENERGY CALCS WILL BE | | RE-REVISED AGAIN TO SHOW HOME SPECIFIC | | ORIENTATION. RE-RESUBMIT REVISED ENERGY | | CALCULATIONS. | | | | 2- NEED TO APPLY FOR SHUTTERS PERMIT. | | | | 3- REVISE ROOF FRAMING PLAN BY THE ENTRY | | PORCH. CONCRETE BEAM DOESN'T EXTEND ALL | | THE WAY BACK TO THE FOYER AREA. ALSO, | | KNEEWALL AREA DOESN'T HAVE CONCRETE | | BEAMS EITHER. REVISE AS REQUIRED AND | | SPECIFY CORRESPONDING TRUSS CONNECTORS. | | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. | | | | 4- TRUSS ANCHOR SCHEDULE: REVISE NUMBER | | OF NAILS FOR HUS26. SEE 2005 CATALOGUE. | | | | 5- WINDOW MULLION SPECIFIED FOR GREAT | | ROOM FIXED WINDOWS DON'T RESIST THE | | DESIGN PRESSURES. RE-REVISE AS REQUIRED. | | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. | | | | 6- PROVIDE PRODUCT APPROVAL FOR: | | A) 1 HR FIRE RATED INSWING DOOR AS SHOWN | | IN ATRIUM PLANS. | | | | B) WINDOW MULLION SPECIFIED FOR GREAT | | ROOM FIXED WINDOWS AS RE-REVISED BY THE | | ARCHITECT. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712. |
|