Plan Review Notes For Permit 05060458
Permit Number 05060458
Review Stop B
Sequence Number 1
Notes
Date Text
2005-07-05 00:00:00BUILDING REVIEW PROVISO:
 1- SHUTTERS UNDER A SEPARATE PERMIT.
 2- SUBMIT REVISED ENERGY CALCULATIONS
 FOR WORST CASE SCENARIO.
 3- ROOF FRAMING PLAN: REVISE CONNECTOR
 SPECIFIED AT FRONT PORCH MASONRY BEAMS.
 SEE DETAILS 4/D1 AND 5/D1.
 4- TRUSS ANCHOR SCHEDULE: REVISE NAIL
 SIZE FOR HUS26. SEE CATALOGUE.
 5- PROVIDE FLORIDA PRODUCT APPROVAL FOR:
 A) 1 HR FIRE RATED DOOR EGRESS ASSEMBLY.
 FLORIDA PRODUCT APPROVAL TO MATCH NOA.
 BENCHMARK AND THERMA TRU ARE 2 DIFFERENT
 MODELS.
 B) FIXED WINDOWS MISSING FLORIDA PAGES.
 C) SINGLE HUNG WINDOWS MISSING FL. PAGES
 D) ROOF TILE NEEDS FLORIDA PAGES WITH
 MATCHING REPORT.
 6- WINDOW MULLIONS: CLEARLY SPECIFY SIZE
 OF MULLION AND ANCHORS TO BE USED IN
 FIXED WINDOW AT GREAT ROOM. SE DESIGN
 PRESSURES ON PLANS. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 7- PROVIDE CLEAR WINDOW/DOOR SCHEDULES
 WITH MATCHING SIZES AND SYMBOLS USED.