Plan Review Notes For Permit 05060452 |
Permit Number |
05060452 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-06-07 00:00:00 | DENIED: | | CALLED CONTRACTOR NO ANSWER MACHINE & NO | | ANSWER. | | 1.PROVIDE FRESH AIR CALCULATIONS IN | | ACCORDANCE WITH 2001 FBC(M) TABLE 403.3. | | | | 2.PLEASE PROVIDE INFORMATION ON THE | | EXISTING WAREHOUSE; INDICATE WHAT IS | | STORED OR WHAT TYPE OF WORK WILL BE DONE | | IN THE WAREHOUSE AREA. | | | | 3.INDICATE TERMINATION OF THE | | CONDESATE; MINIMUM OF 12" FROM THE | | BUILDING STRUCTURE PER 2001 FBC | | 1503.4.4. | | | | 4.FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | WITH NOTIFICATION TO ALARM/STROBE PER | | 2001 FBC(M)606.2.1 & 606.4.1(2). | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|