2005-06-07 00:00:00DENIED:
 CALLED CONTRACTOR NO ANSWER MACHINE & NO
 ANSWER.
 1.PROVIDE FRESH AIR CALCULATIONS IN
 ACCORDANCE WITH 2001 FBC(M) TABLE 403.3.
  
 2.PLEASE PROVIDE INFORMATION ON THE
 EXISTING WAREHOUSE; INDICATE WHAT IS
 STORED OR WHAT TYPE OF WORK WILL BE DONE
 IN THE WAREHOUSE AREA.
  
 3.INDICATE TERMINATION OF THE
 CONDESATE; MINIMUM OF 12" FROM THE
 BUILDING STRUCTURE PER 2001 FBC
 1503.4.4.
  
 4.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION TO ALARM/STROBE PER
 2001 FBC(M)606.2.1 & 606.4.1(2).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.