Date |
Text |
2005-07-07 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| 1. SHT A-1 SUBMIT A DETAIL FOR THE SINK |
| IN THE LOUNGE THAT SHOWS COMPLIANCE WITH |
| SECTION 11-4.24 AND ALL SUBSECTIONS. |
| SHOW: |
| A. 11-4.24.2 HEIGHT |
| B. 11-4.24.3 KNEE CLEARANCE |
| C. 11-4.24.4 SINK DEPTH |
| D. 11-4.24.5 CLEAR FLOOR SPACE SHALL BE |
| PROVIDED TO ALLOW FORWARD APPROACH AND |
| SHALL EXTEND UNDERNEATH THE SINK A |
| MAXIMUM OF 19". - CABINET DOORS ARE NOT |
| ALLOWED IN THE CLEAR FLOOR SPACE. |
| E. 11-4.24.6 EXPOSED PIPES & SURFACES |
| F. 11-4.24.7 FAUCETS |
| 2. SUBMIT A WATER RISER DIAGRAM SHOWING |
| ALL PIPE SIZES, VALVES, WATER HAMMER |
| ARRESTORS, (IF REQUIRED BY 604.9), AND |
| POINT OF CONNECTION. SECTION 104.3.1.1. |
| 3. SUBMIT A SANT. RISER DIAGRAM SHOWING |
| ALL PIPE SIZES, VENTS, AND POINT OF |
| CONNECTION. SECTION 104.3.1.1. |
| 4. THE PRINTED NAME OF THE PERSON |
| SEALING THE DOCUMENT SHALL BE ON THE |
| TITLE BLOCK OF EACH SHEET. FAC |
| 61G1-16.004(6) AND FS 481.2055. |
| 5. THE PERSONAL SIGNATURE SHALL APPEAR |
| ON ALL ARCHITECTURAL DOCUMENTS TO BE |
| FILED FOR PUBLIC RECORD. WHAT APPEARS TO |
| BE INITIALS ARE ON THE SEAL OF EACH |
| SHEET. PLEASE PROVIDE A SIGNED, SEALED, |
| DATED, NOTORIZED LETTER INDICATING YOUR |
| LEGAL SIGNATRUE FOR OUR RECORDS TO |
| VERIFY YOUR SIGNATURE. FAC 61G1-16.003 |
| AND FS 481,2055. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 653-2692 |
| E-MAIL [email protected] |