Plan Review Notes For Permit 05060432 |
Permit Number |
05060432 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-06-22 00:00:00 | ******* UNSAT ******* | | | | 1)NOTE: PLEASE CLARIFY NEW AND EXSITING | | ELECTRICAL SERVICE EQUIPMENT. ONLY ONE | | PANEL IS INDICATED AS EXISTING. THIS | | PANEL IS ALSO ABBREVIATED AS "GEN. | | PANEL". THIS ABBRVIATION INDICATES THIS | | PANEL AS "GENERATOR"? PANEL? | | PLEASE PROVIDE ALL INFORMATION ON ALL | | NEW PANELS ETC SHOWN BEING INSTALLED. | | AMERAGE, ETC, TRANSFORMER ETC, CONDUIT, | | CONDCUTORS , GROUNDING, 250.30., MCB | | REQUIRED ON LOAD SIDE OF TRANSFORMER IN | | PANEL. PLEASE SEE 408.16,240.21 | | IF ALL IS EXSITING?, PLEASE LABEL | | ACCORDINGLY. | | 215.5 | | | | 2)NOTE: PLEASE SEE CIRCUITING FOR EM/EXT | | LTS NEW OR EXSTING? PLEASE SEE 700.12E | | FOR CIRCUITING. | | | | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND | | ONLY INSERT NEW REVISED SHEETS INTO | | COMPLETE SETS FOR REVIEW AND STAMPING. | | PLEASE SEE ANY POSSIBLE COMMENTS FROM | | OTHER REVIEWER(S) WHICH MAY HAVE AN | | AFFECT ON ELECTRICAL PLANS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|