Notes
Date Text
2005-06-22 00:00:00******* UNSAT *******
  
 1)NOTE: PLEASE CLARIFY NEW AND EXSITING
 ELECTRICAL SERVICE EQUIPMENT. ONLY ONE
 PANEL IS INDICATED AS EXISTING. THIS
 PANEL IS ALSO ABBREVIATED AS "GEN.
 PANEL". THIS ABBRVIATION INDICATES THIS
 PANEL AS "GENERATOR"? PANEL?
 PLEASE PROVIDE ALL INFORMATION ON ALL
 NEW PANELS ETC SHOWN BEING INSTALLED.
 AMERAGE, ETC, TRANSFORMER ETC, CONDUIT,
 CONDCUTORS , GROUNDING, 250.30., MCB
 REQUIRED ON LOAD SIDE OF TRANSFORMER IN
 PANEL. PLEASE SEE 408.16,240.21
 IF ALL IS EXSITING?, PLEASE LABEL
 ACCORDINGLY.
 215.5
  
 2)NOTE: PLEASE SEE CIRCUITING FOR EM/EXT
 LTS NEW OR EXSTING? PLEASE SEE 700.12E
 FOR CIRCUITING.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  