Plan Review Notes For Permit 05060425 |
Permit Number |
05060425 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-08-03 00:00:00 | | | | | | | SAME COMMENTS AS PREVIOUS REVIEW: | | PLEASE SUBMIT DETAILS FOR THE PANEL | | SHOWN ON THE SCHEMATIC, FEEDER AND CONDU | | IT SIZE AND TYPE, PANEL RATING AND OCP, | | PANEL SCHEDULE AND COMPUTED LOAD, ETC. | | IF AN ELECTRIC HEATER IS TO BE INSTALLED | | PLEASE SUBMIT CALCULATIONS FOR THE MAIN | | SERVICE. PANEL SHOWN DOES NOT APPEAR ON | | THE BUILDING PLAN ON FILE. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | | | |
|