Plan Review Notes
Plan Review Notes For Permit 05060413
Permit Number 05060413
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2005-06-13 00:00:001) NEW FIRE ALARM SYSTEMS SHALL BE
 LISTED FOR CENTRAL STATION SERVICE.
  
 2) ALL FIRE ALARM SYSTEMS THAT SUPERVISE
 FIRE SPRINKLER SYSTEMS SHALL BE UL
 CERTIFICATED AND HAVE DOCUMENT ATTESTING
 TO THIS CERTIFICATION PRIOR TO FINAL
 APPROVAL OF THE FIRE ALARM SYSTEM.
  
 3) THE FIRE ALARM SYSTEM SHALL BE CLASS
 "A" OR FULLY ADDRESSABLE.
  
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL
 561-835-2935 OR 561-805-6722