Plan Review Notes For Permit 05060145 |
Permit Number |
05060145 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-10-06 00:00:00 | DENIED; | | 1.PIPING DIAGRAM DOES NOT MATCH POOL | | LAYOUT. SPA PIPING MISSING, AND LION | | HEADS NOT SHOWN ON POOL DRAWING. | | 2ND REQUEST FOR NOTES; | | 2) FBC-2001 424.2.12.1 PRESSURE TESTS. | | PER MANUFACTURE RECOMMENDATIONS, NO AIR | | TEST SHALL BE APPROVED FOR PVC PIPE AND | | FITTINGS. (ADD TO NOTES) | | 3) FBC-2001 SEC 424.2.6.1 ENGINEERING | | DESIGN, CONSTRUCTION AND WORKMANSHIP. | | ANSI/NSPI-5. (ADD TO NOTES) | | 4) FBC-2001 424.2.14.1 SWIMMING POOL | | WATER HEATERS SHALL BEAR THE LABEL OF A | | RECOGNIZED TESTING AGENCY. MANUFACTURE | | SHEETS REQUIRED. (SUBMITTAL) | | 5)FBC-2001 424.2.9 WATER SUPPLY, LOCAL | | ORD. #2853-95, BACKFLOW REQUIRED ON THE | | WATER SERVICE. (ADD TO NOTES) | | 6)FBC-2001 424.2.13.2 JOINTS AND | | CONNECTIONS, FBC PLUMBING SEC. 606.21, | | PURPLE PRIMER REQUIRED ON PVC PIPES AND | | FITTINGS. (ADD TO NOTES) | | 7.FBC-2001 424.2.15 GAS PIPING SHALL | | COMPLY WITH FBC FUEL GAS. SEPARATE PLANS | | AND PERMIT ARE REQUIRED. (ADD TO NOTES) | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 | | |
|