Plan Review Notes
Plan Review Notes For Permit 05060145
Permit Number 05060145
Review Stop P
Sequence Number 2
Notes
Date Text
2005-10-06 00:00:00DENIED;
 1.PIPING DIAGRAM DOES NOT MATCH POOL
 LAYOUT. SPA PIPING MISSING, AND LION
 HEADS NOT SHOWN ON POOL DRAWING.
 2ND REQUEST FOR NOTES;
 2) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 3) FBC-2001 SEC 424.2.6.1 ENGINEERING
 DESIGN, CONSTRUCTION AND WORKMANSHIP.
 ANSI/NSPI-5. (ADD TO NOTES)
 4) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 5)FBC-2001 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON THE
 WATER SERVICE. (ADD TO NOTES)
 6)FBC-2001 424.2.13.2 JOINTS AND
 CONNECTIONS, FBC PLUMBING SEC. 606.21,
 PURPLE PRIMER REQUIRED ON PVC PIPES AND
 FITTINGS. (ADD TO NOTES)
 7.FBC-2001 424.2.15 GAS PIPING SHALL
 COMPLY WITH FBC FUEL GAS. SEPARATE PLANS
 AND PERMIT ARE REQUIRED. (ADD TO NOTES)
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  