Plan Review Notes
Plan Review Notes For Permit 05060145
Permit Number 05060145
Review Stop P
Sequence Number 1
Notes
Date Text
2005-06-20 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 A. FOLLOWING INFORMATION REQUIRED ON
 PLANS:
  
 1) COMPLY WITH FBC-2001 SEC 424.2
 PRIVATE SWIMMING POOLS. (ADD TO NOTES).
 2) FBC-2001 SEC 424.2.6.1 ENGINEERING
 DESIGN, CONSTRUCTION AND WORKMANSHIP.
 ANSI/NSPI-5. (ADD TO NOTES).
 3) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES).
 4) FBC-2001 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON THE
 WATER SERVICE. (ADD TO NOTES).
 5) FBC-2001 424.2.13.2 JOINTS AND
 CONNECTIONS, FBC PLMG SECT. 605.21,
 PURPLE PRIMER REQUIRED ON PVC PIPES AND
 FITTINGS. (ADD TO NOTES).
 6) FBC-2001 424.2.15 GAS PIPING SHALL
 COMPLY WITH FBC FUEL GAS. SEPARATE PLANS
 AND PERMIT ARE REQUIRED. (ADD TO NOTES).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]