Date |
Text |
2005-08-03 00:00:00 | IN ELECTRIC FOR REVIEW. |
| CALLED CONTRACTOR TO GO OVER ELECTRICAL |
| PLANS SUBMITTED. NO SPECS FOR ATS , ETC |
| SUBMITTED. |
| ENGINEER TO BE CALLED BY CONTRACTOR TO |
| GO OVER ELECTRICAL. |
| ****** UNSAT 2ND REVIEW ****** |
| |
| PLEASE SEE SOME NOTES FROM PREVIOUS |
| REVIEW STILL NEED TO BE ADDRESSED. |
| |
| THESE ARE TAKEN DIRECTLY FROM PREVIOUS |
| REVIEW AND RESPONSE LTR SUBMITTED. |
| |
| 1)NOTE: NOTE #1, OK. |
| |
| 2)NOTE: NOTE #2, OK, EXCEPTION FOR OCP |
| AT GEN OK. |
| |
| 3)NOTE: NOTE #3, NO, PLEASE SEE SPEC |
| BOOKS WERE SUBMITTED SHOWING A DIFFERENT |
| RATING. |
| PLEASE NOW, SEE ALL SPECS FOR GENERATOR, |
| SUB-BASE FUEL TANK, ATS ETC WERE NOT |
| SUBMITTED BACK WITH PLANS AND PERMIT |
| APPLICATION. THIS IS REQUIRED FOR |
| REVIEW. |
| |
| 4)NOTE: NOTE #4 NO,PLEASE SEE |
| 225.31,-225.36 AS NOTED ON PREVIOUS |
| REVIEW.THE DISCONNECTING MEANS ON |
| GENERATOR IS NOT AN ACCEPTABLE MEANS OF |
| DISCONNECT REQUIRED. |
| |
| 5)NOTE: NOTE #5 NO. PREVIOUS NOTES. |
| 225.36 |
| |
| 6)NOTE: NOTE #6, OK, CORRECTED. |
| |
| 7)NOTE: NOTE #7 NO. PLEASE SEE RESPONSE |
| LTR MENTIONS "NO SPECS SUBIMTTED" , |
| HOWEVER PLEASE CONTACT ELECTRICAL |
| CONTRACTOR AS REQUIRED SPECS WERE INDEED |
| SUBMITTTED FOR REVIEW ON ORIGINAL |
| SUBMITTED PACKAGE. |
| GROUND FOR FOOTER STEEL ADDED, OK. |
| NOTE FOR GENERATOR BEING A "SEPARATELY |
| DERIVED SYSTEM" SHOULD BE ADDED TO |
| RISER. IT IS KNOWN THAT THE ATSSHOWN |
| ON PLANS IS A 4-POLE ATS FOR SEPARATELY |
| DERIVED SYSTEMAND ALSO NOTED THATTHE |
| NEUTRAL TO GROUNDWAS SHOWN TO NEW |
| GROUNDING ELECTRODE SYSTEM. PLEASE SEE |
| SPECS SUBMITTED, (NOT PART OF ENGINEER'S |
| PLANS) INDICATED A 3-POLE ATS AND WAS |
| THE REASON FOR COMMENT. |
| |
| NEW NOTE: |
| |
| 8)NOTE: PLEASE SEE ONLY ONE COPY OF |
| ORIGINALASP-1/A_1 SHEETS/SETS WERE |
| SUBMITTED. IT IS NOTED THAT NEW A-1 |
| SHEETS WERE SUBMITTED, HOWEVER 2ND COPY |
| OF ASP-1 WAS NOT SUBMITTED BACK WITH |
| SET. |
| |
| ************************************* |
| PLEASE REMOVE ANY OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW REVISED SHEETS INTO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| PLEASE SUBMIT TWO COMPLETE SETS FOR |
| REVIEW AND STMAPING. |
| ONCE AGAIN, IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |