2005-06-22 00:00:00 | **********UNSAT ************** |
| |
| 1)NOTE: PLEASE SEE 250.30 FOR GROUNDING |
| OF TRANSFORMER AS SHOWN. |
| PLEASE SEE THIS MUST ALSO TIE INOT |
| EXISTING EFFECTIVE GROUNDING ELECTRODE |
| SYSTEM. |
| |
| 2)NOTE: PLEASE SEE 445.13 FIR MIN SIZING |
| OF CONDUCTORS FROM GEN. |
| PLEASE SEE 310.16 |
| |
| 3)NOTE: PLEASE CORRELATE KW RATING OF |
| GEN. FROM PLANS TO SPEC BOOK SUBMITTED. |
| 310,300? |
| 215.5 |
| |
| 4)NOTE: PLEASE SEE A MAIN OR MCB IN |
| EHVAC WILL BE REQUIRED. PLEASE SEE |
| 225.31-225.36 |
| PLEASE INDICATE HOW AND WHICH METHOD OF |
| DISCONNECT WILL BE TAKEN. |
| |
| 5)NOTE: PLEASE SEE SPECS FOR TRANSFER |
| SWITCH SUBMITTED DOES NOT INDICATE IF |
| EQUIPMENT IS "SERVICE ENT RATED". |
| 215.5 |
| |
| 6)NOTE: PLEASE SEE 450.3 FOR AS MAX OCP |
| FOR TRANSFORMER TO BE 125%. |
| |
| 7)NOTE: PLEASE VERIFY NEW GEN SHOWN |
| INDICATES BEING A SEPARATELY DERIVED |
| SYSTEM, HOWEVER AN EQUIPMENT GROUNDING |
| CONDUCTOR IS BEING SHOWN FROM GEN TO |
| EXIST SYSTEM? |
| PLEASE ALSO SEE ONLY GRND ROD IS SHOWN? |
| PLEASE SEE ANY NEW FOOTER STEEL WILL |
| ALSO BE REQUIRED TO BE BONDED AND OR |
| USED AS THE GROUNDING ELECTRODE IF IT |
| MEETS 250.50. |
| PLEASE ALSO SEE SPEC BOOK INDICATES A |
| 3POLE ATS? |
| |
| PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| OTHER REVIEWER(S) WHICH MAY HAVE AN |
| AFFECT ON ELECTRICAL PLANS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |