Plan Review Notes For Permit 05051997 |
Permit Number |
05051997 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-07-14 00:00:00 | BUILDING REVIEW CHECKLIST: | | | | 1- MODIFIED BITUMEN ROOFING SYSTEM | | SELECTED DOESN'T WORK FOR THIS WIND ZONE | | AREA (140MPH). SELECTED SYSTEM IS | | LIMITED BY LIMITATION #9 WHICH DOESN'T | | ALLOW FOR ADDITIONAL NAIL ENHANCING TO | | RESIST UPLIFT LOADS AT CORNERS AND | | PERIMETER AS REQUIRED BY TABLE 1606.2B | | FBC 2001. NEED TO SELECT ANOTHER SYSTEM | | THAT WILL RESIST SUCH LOADS OR THAT | | COULD BE ENHANCED WHEN LIMITATION #7 IS | | SPECIFIED. | | | | 2- NOTICE OF COMMENCEMENT IS EXPIRED | | AFTER 90 DAYS OF NO WORK. NEED TO | | RE-RECORD NOTICE OF COMMENCEMENT. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ AT (561)805-6712. |
|