2005-09-13 00:00:00BUILDING REVIEW THIRD CHECKLIST:
 1- OPENINGS FROM THE GARAGE DIRECTLY
 INTO A ROOM USED FOR SLEEPING PURPOSES
 IS NOT ALLOWED. SEC. 411.2.8 FBC 2001.
 "THEATER" ROOM NEXT TO THE GARAGE IS SET
 UP AS A BEDRM. THERE IS A CLOSET IN THE
 ROOM AND ELECTRICAL PLAN SHOWS SMOKE
 DETECTORS IN AND OUT OF THE ROOM WHEN
 REQUIRED FOR SLEEPING ROOMS. REVISE AS
 REQUIRED.
  
 2- NEED A COMPLETE BATHROOM WITH DOOR
 THAT ALLOWS 29" MIN. CLEAR OPENING AS
 REQUIRED BY SEC. 11-11 FBC 2001.
  
 3- PRODUCT APPROVALS FOR DOORS/WINDOWS
 SUBMITTED ARE FOR IMPACT GLAZING. THIS
 HOUSE IS SUPPOSED TO HAVE NON-IMPACT
 GLAZING. PROVIDE CORRECT PRODUCT
 APPROVAL FOR:
 A) FRENCH DOORS.
 B) FIXED WINDOWS.
 C) SINGLE HUNG WINDOWS.
 D) SLIDING GLASS DOORS
 E) CASEMENT WINDOWS.
  
 4- NEED TO SPECIFY SAFETY GLASS FOR
 WINDOWS AT HER BATH BY THE WHIRPOOL.
 SEC. 2405.2.1 FBC 2001. INFORMATION
 SUBMITTED WAS FOR IMPACT GLASS. THAT'S
 WHY THIS COMMENT WAS NOT ADDRESSED ON
 PREVIOUS CHECKLIST.
  
 5- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 6- PROVIDE COMPLETE SPECS FOR BBQ HOOD
 FOR EXTERIOR USE AND SPECS FOR SPECIFIC
 GRILL TO BE INSTALLED.
  
 7- PROVIDE COPY OF PAID IMPACT FEES
 RECEIPT THAT CORRESPONDS TO THIS HOUSE.
 RECEIPT SUBMITTED IS FOR ANOTHER HOUSE.
  
 8- A) PROVIDE COMPLETE UL LISTING AND
 SPECS FOR TWO SIDED FIREPLACE AS SHOWN
 ON PLANS. INFORMATION SUBMITTED DOESN'T
 MATCH PLANS.
  
 B) PROVIDE COMBUSTION AIR CALCULATIONS
 FOR VENTLESS FIREPLACE FOR MECHANICAL
 PLANS EXAMINER REVIEW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.
  
  
  