2005-09-13 00:00:00 | BUILDING REVIEW THIRD CHECKLIST: |
| 1- OPENINGS FROM THE GARAGE DIRECTLY |
| INTO A ROOM USED FOR SLEEPING PURPOSES |
| IS NOT ALLOWED. SEC. 411.2.8 FBC 2001. |
| "THEATER" ROOM NEXT TO THE GARAGE IS SET |
| UP AS A BEDRM. THERE IS A CLOSET IN THE |
| ROOM AND ELECTRICAL PLAN SHOWS SMOKE |
| DETECTORS IN AND OUT OF THE ROOM WHEN |
| REQUIRED FOR SLEEPING ROOMS. REVISE AS |
| REQUIRED. |
| |
| 2- NEED A COMPLETE BATHROOM WITH DOOR |
| THAT ALLOWS 29" MIN. CLEAR OPENING AS |
| REQUIRED BY SEC. 11-11 FBC 2001. |
| |
| 3- PRODUCT APPROVALS FOR DOORS/WINDOWS |
| SUBMITTED ARE FOR IMPACT GLAZING. THIS |
| HOUSE IS SUPPOSED TO HAVE NON-IMPACT |
| GLAZING. PROVIDE CORRECT PRODUCT |
| APPROVAL FOR: |
| A) FRENCH DOORS. |
| B) FIXED WINDOWS. |
| C) SINGLE HUNG WINDOWS. |
| D) SLIDING GLASS DOORS |
| E) CASEMENT WINDOWS. |
| |
| 4- NEED TO SPECIFY SAFETY GLASS FOR |
| WINDOWS AT HER BATH BY THE WHIRPOOL. |
| SEC. 2405.2.1 FBC 2001. INFORMATION |
| SUBMITTED WAS FOR IMPACT GLASS. THAT'S |
| WHY THIS COMMENT WAS NOT ADDRESSED ON |
| PREVIOUS CHECKLIST. |
| |
| 5- NEED RECORDED NOTICE OF COMMENCEMENT. |
| |
| 6- PROVIDE COMPLETE SPECS FOR BBQ HOOD |
| FOR EXTERIOR USE AND SPECS FOR SPECIFIC |
| GRILL TO BE INSTALLED. |
| |
| 7- PROVIDE COPY OF PAID IMPACT FEES |
| RECEIPT THAT CORRESPONDS TO THIS HOUSE. |
| RECEIPT SUBMITTED IS FOR ANOTHER HOUSE. |
| |
| 8- A) PROVIDE COMPLETE UL LISTING AND |
| SPECS FOR TWO SIDED FIREPLACE AS SHOWN |
| ON PLANS. INFORMATION SUBMITTED DOESN'T |
| MATCH PLANS. |
| |
| B) PROVIDE COMBUSTION AIR CALCULATIONS |
| FOR VENTLESS FIREPLACE FOR MECHANICAL |
| PLANS EXAMINER REVIEW. |
| |