2005-08-15 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1- NEED RECORDED NOC. |
| |
| 2- CLARIFY IF USING STORM SHUTTERS OR |
| IMPACT GLAZING. THERE IS A NOTE SAYING |
| THAT SHUTTERS WILL BE DONE UNDER |
| SEPARATE PERMIT. BUT, PRODUCT APPROVALS |
| SUBMITTED ARE FOR NON-IMPACT AND IMPACT |
| GLAZING. PROVIDE COMPLETE PRODUCT |
| APPROVALS FOR IMPACT OR FOR NON-IMPACT. |
| |
| 3- PROVIDE FLORIDA OR APPLY FOR LOCAL |
| PRODUCT APPROVAL FOR SLIDING GLASS DOORS |
| AS SHOWN ON PLANS. PRODUCT APPROVAL |
| SUBMITTED IS FOR A DIFFERENT |
| CONFIGURATION OF DOORS. |
| |
| 4- A) PROVIDE COMPLETE SPECS AND |
| APPROVED LISTING FOR BBQ. INCLUDING |
| MODEL SELECTED. |
| B) PROVIDE SPECS AND APPROVED LISTING |
| FOR HOOD TO BE USED OUTDOOR. |
| |
| 5- CLARIFY IF USING CEMENT OR CLAY TILE. |
| ELEVATIONS CALL FOR CONCRETE ROOF TILE. |
| TYP. WALL SECTION IN SHEET A6 CALLS FOR |
| CLAY BARREL TILE AND PRODUCT APPROVAL |
| SUBMITTED IS FOR CONCRETE TILE. CLARIFY. |
| |
| 6- PROVIDE PRODUCT APPROVAL FOR |
| 2"X6"X1/8" MULLION. |
| |
| 7- PROVIDE COPY OF THE IMPACT FEES PAID |
| RECEIPT. |
| |
| 8- SHEET A1: COLUMNS AT LANAI ARE C4, |
| NOT C2. REVISE AS REQUIRED. |
| |
| 9- SHEET A3: SPECIFY CONNECTOR FOR |
| GIRDER TRUSS RESTING ON (3)2X6 POST. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| |