2005-07-12 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1- NEED RECORDED NOTICE OF COMMENCEMENT. |
| |
| 2- UPDATE GENERAL NOTES IN SHEET T1. SEE |
| CHAPTER 19 AND 35 FBC 2001 FOR PROPER |
| STANDARD REFERENCE AND EDITION. ALSO, |
| SEE SEC. 2405.2 FBC 2001 AND REVISE |
| SAFETY GLAZING NOTE AS REQUIRED. |
| |
| 3- DESIGN PARAMETERS: WHY MINIMUM SOIL |
| BEARING PRESSURE IS : NA?. |
| |
| 4- PROVIDE COMPLETE BBQ SPECS AND |
| LISTING FOR INSTALLATION IN PORCH. SEC. |
| 2808 FBC 2001. |
| |
| 5- FOOTING BETWEEN GARAGE AND CLUB ROOM |
| DON'T MATCH DETAIL 5. REVISE AS REQUIRED |
| |
| 6- REVISE/UPDATE ALL TRUSS ANCHORS NAIL |
| SIZE AND NUMBER TO MATCH CATALOGUE THAT |
| WAS REVISED TO COMPLY WITH SEC. 1609.4.3 |
| FBC 2001. PROVIDE TESTING & ENGINEERING |
| FOR TYPE AND NUMBER OF NAILS THAT DIFFER |
| FROM THOSE TESTED AND PUBLISHED BY THE |
| MANUFACTURER. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| |
| 7- CONNECTOR THD210 IS A WOOD TO WOOD |
| CONNECTOR. SEE CATALOGUE FOR PROPER |
| MASONRY CONNECTOR AND REVISE AS REQ'D. |
| |
| 8- SPECIFY MULLION SIZE AND ANCHORS FOR |
| FIXED WINDOWS AT LIVING ROOM. SIZE OF |
| MULLION SHOWN ON PRODUCT APPROVAL |
| SUBMITTED DOESN'T RESIST THE DESIGN |
| PRESSURES CALCULATED ON PLANS. SEC. |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| |
| 9- PROVIDE FLORIDA OR LOCAL PRODUCT |
| APPROVAL FOR: |
| A) SLIDING GLASS DOORS. DADE COUNTY NOA |
| AND FLORIDA REPORT DON'T CORRESPOND TO |
| EACH OTHER. |
| |
| B) WINDOW MULLION SIZE AS SPECIFIED ON |
| PLANS FOR LIVING ROOM WINDOWS. |
| |
| C) CASEMENT WINDOWS. NEED THE FLORIDA |
| PRODUCT APPROVAL PART. MAKE SURE DADE |
| COUNTY NOA MATCHES FLORIDA REPORT AND |
| ASSEMBLY SHOWN ON PLANS. |
| |
| D) ROOF TILE. NEED FLORIDA PRODUCT |
| APPROVAL. MAKE SURE REPORT SUBMITTTED IS |
| THE SAME ONE SUBMITTED FOR FLORIDA |
| PRODUCT APPROVAL. |
| |
| 10- OWES #206.76 FOR UPDATED VALUATION. |
| GUEST ROOM WAS NOT CONSIDERED IN A/C |
| AREA DECLARED IN APPLICATION. |
| |
| 11- SPECIFY COLUMNS AT MASTER BEDROOM |
| BAY WINDOW. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. SEE SHEET A1. |
| |
| 12- DETAIL E/A3: CLARIFY WHY USING 6" |
| BOLTS INTO CONCRETE. THERE IS NOT |
| CONCRETE TO ATTACH TO. REVISE AS REQ'D. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| JULIO GOMEZ AT (561)805-6712. |
| |