2005-07-12 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1- NEED RECORDED NOTICE OF COMMENCEMENT. |
| |
| 2- UPDATE GENERAL NOTES ON SHEET T1. SEE |
| CHAPTER 19 AND 35 FOR PROPER STANDARD |
| REFERENCE AND EDITION. ALSO, SEE SEC. |
| 2405.2 FBC 2001 AND REVISE SAFETY |
| GLAZING NOTE AS REQUIRED. |
| |
| 3- DESIGN PARAMETERS. CLARIFY WHY THE |
| MIN. SOIL BEARING PRESSURE IS NA?. |
| |
| 4- PROVIDE COMPLETE SPECS AND LISTING |
| FOR BBQ TO BE INSTALLED IN THE PORCH. |
| SEC. 2808 FBC 2001. |
| |
| 5- REVISE COLUMNS SPECIFIED FOR LANAI. |
| THEY ARE C4 COLUMNS, NOT C2. |
| |
| 6- REVISE /UPDATE ALL TRUSS ANCHORS TO |
| MATCH NAIL SIZE AND NUMBER ON REVISED |
| CATALOGUE TO COMPLY WITH SEC. 1609.4.3 |
| FBC 2001. PROVIDE TESTING AND |
| ENGINEERING FOR NAIL SIZE AND NUMBER |
| THAT DIFFER FROM THOSE ALREADY TESTED |
| AND PUBLISHED BY THE MANUFACTURER. SEC. |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| |
| 7- CONNECTOR THD210 IS A WOOD TO WOOD |
| CONNECTOR. SEE CATALOGUE FOR PROPER |
| MASONRY CONNECTOR AND REVISE AS REQUIRED |
| |
| 8- SPECIFY MULLION SIZE AND ANCHORS FOR |
| FIXED WINDOWS AT LIVING ROOM. SEE |
| PRODUCT APPROVAL TO VERIFY THAT THEY |
| RESIST THE CALCULATED DESIGN PRESSURES. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| |
| 9- PROVIDE FLORIDA OR LOCAL PRODUCT |
| APPROVAL FOR: |
| A) CASEMENT WINDOWS. NEED FLORIDA |
| PRODUCT APPROVAL. |
| |
| B) SLIDING GLASS DOORS AS SHOWN ON |
| PLANS. |
| |
| C) WINDOW MULLION SIZE AS SPECIFIED ON |
| PLANS FOR LIVING ROOM WINDOWS. |
| |
| 10- REVISE ENERGY CALCULATIONS. NEED |
| WORST CASE SCENARIOCALCULATIONS WHEN |
| USING IT FOR A MODEL. |
| |
| 11- CLARIFY WHY USING ONLY AN F |
| CONNECTOR FOR END OF GIRDER TRUSS ABOVE |
| ENTRY OF BEDROOM #3. SPECIFY CALCULATED |
| UPLIFT LOADS. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| |
| 12- REAR ELEVATION DON'T MATCH PLANS. |
| SEE BREAKFAST AREA AND CABANA BATH. |
| REVISE AS REQUIRED. |
| |