Notes |
Date |
Text |
2005-06-07 00:00:00 | DENIED: | | 1.PLEASE PROVIDE OUTSIDE AIR | | CALCULATIONS PER 2001 FBC/M TABLE 403.3. | | | | 2.INDICATE OUTSIDE AIR INTAKE, LAYOUT, | | DUCT SIZE AND MATERIAL. | | | | 3.PLEASE CLARIFY LOCATION OF THE AHU. | | IS IT LOCATED IN A CLOSET SEPARATE FROM | | THE BATHROOM/STORAGE AREA?MECAHNICAL | | CLOSETS SHALL COMPLY WITH 2001 FBC/M | | 603.9. | | | | 4.PLEASE CLARIFY THE OFFICE 1 AND 2 | | ARE OCCUPIED BY THE SAME TENANT.PLEASE | | NOTE, IF NOT TENANT IN OFFICE 2 SHALL BE | | ABLE TO TEMPERATURE CONTROL OF THEIR | | SPACE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|