Plan Review Notes For Permit 05051815 |
Permit Number |
05051815 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-06-14 00:00:00 | DENIED: | | 1.PLANS NOR APPLICATION INDICATE FUEL | | SOURCE (NATURAL GAS, PROPOANE OR DIESEL | | FUEL, ETC).INDICATE GAS PERMIT IF | | AVAILABLE. | | | | 2.PLANS DO NOT INDICATE LOCATION OF | | FUEL SOURCE. | | | | 3.MANUFACTURER'S SUBMITTAL DATA DOES | | NOT INDICATE CLEARANCES FROM ADJACENT | | BUILDINGS, PROPERTY LINES, FRESH AIR | | INTAKES I.E., DOORS, WINDOWS, GRILLES IN | | SOFFITS.LOCATION SHALL COMPLY WITH | | 2001 FBC(M) 804.3.4 & 804.3.5. | | | | PLEASE NOTE, PROPANE GAS & TANK | | INSTALLATION SHALL COMPLY WITH NFPA 58 | | FOR LOCATION OF TANKS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|