Plan Review Notes For Permit 05051815 |
Permit Number |
05051815 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-06-11 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} PLEASE PROVIDE A RISER DIAGRAM | | INDICATING WHERE THE TRANSFER SWITCH | | INTEGRATES IN THE SERVICE. | | | | 2} SHOW COMPLIANCE WITH 225.31-36. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|