Plan Review Notes For Permit 05051631 |
Permit Number |
05051631 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-05-27 00:00:00 | | | PLEASE SEE THE CONDUIT TYPES WERE NOT | | SPECIFIED. THE 350 MCM WILL NEED TO BE | | IN A LARGER CONDUITTO COMPLY WITH TABLE | | 10. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|