Plan Review Notes For Permit 05051627
Permit Number 05051627
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2005-07-15 00:00:00******DENIED******
  
 1) THE SURVEY DRAWING ILLUSTRATES STAIRS
 IN THE VICINITY OF THE GENERATOR. IS
 THAT A REQUIRED MEANS OF EGRESS, AND IF
 SO WHAT IS THE DISTANCE BETWEEN THE
 STAIRS AND GENERATOR EXHAUSTING?
  
 2) ALL WORK TO COMPLY WITH NFPA 110 AND
 OTHER APPLICABLE CODES.
  
 3) PLEASE SUBMIT FURTHER DETAILS IN
 REGARDS TO FUEL STORAGE.
  
  
 MIKE WENNERGREN, CAPTAIN
 WPBFR(561) 805-6722 OR 835-2951