Plan Review Notes For Permit 05051565 |
Permit Number |
05051565 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-06-08 00:00:00 | *********UNSAT ********** | | | | 1)NOTE: PLEASE SEE WIRING DIAGRAM | | SUBMITTED SHOWS A RISER DIAGRAM FOR A | | NEW SERVICE. IF A NEW SERVICEIS GOING TO | | BE INSTALLED, THIS MUST BE UNDER A | | SEPARATE PERMIT. | | PLEASE ONLY SUBMIT THE ELECTRICAL WIRING | | DIAGRAM RELATIVE TO POOL. | | IF NEW POOL PANEL IS BEING INSTALLED, | | THEN PLEASE INCLUDE OCP FROM EXISTING | | PANEL(IF EXSITNG) SIZE OF SERVICE ETC. | | PLEASE CLARIFY TYPE OF CONDUIT TO SUB | | PANEL. | | PLEASE SEE TYOE OF CONDUIT APPROVED FOR | | USE AND INSTALLATIONS. ENMT? | | | | 2)NOTE: PLEASE SEE THE NUMBER OS | | CONDUCTORS FROM MAIN PANEL TO SUB PANEL. | | | | THIS SEEMS TO BE MISSING EITHER THE | | NEUTRAL OR EQUIPMENT GROUNDING?? | | 250.110,250.24, ETC. | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|