Plan Review Notes For Permit 05051518 |
Permit Number |
05051518 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-05-20 00:00:00 | CHECKLIST: | | | | 1- FLAT ROOF SYSTEM SELECTED ON THE | | PRODUCT APPROVAL IS LIMITED BY GENERAL | | LIMITATION #9. THIS LIMITATION APPLIES | | TO THE MAXIMUM UPLIFT PRESSURES RESISTED | | BY THE SYSTEM AND NOT ADDITIONAL | | ENHANCEMENT IS ALLOWED. | | NEED SYSTEM THAT RESISTS UPLIFT OF | | -89PSF AT ZONE 3. SEE TABLE 1606.2B FBC | | 2001. | | | | 2- PROVIDE PRODUCT APPROVAL INCLUDING | | ONLY THE SYSTEM TO BE USED IN THIS | | PROJECT. DON'T INCLUDE OTHER SYSTEMS TO | | SAVE PAPER AND EXPEDITE REVIEWPROCESS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ AT (561)805-6712. |
|