2006-04-28 00:00:00DENIED:
 2ND REQUEST:PLEASE REVISE MANUAL J
 CALCULATIONS TO REFLECT THE EXISTING
 UNIT. PLANS INDICATE A 3 TON UNIT AND
 THE MANUAL J SHOWS A 2.2 TON.
  
 RETURN AIR REQUIRED FROM THE NEW STUDY
 ROOM.
  
 PROVISO:
 THE NEW BATHROOM SHALL HAVE A WINDOW
 WITH A MINIMUM OPENING OF 3 SQUARE FEET
 OR AN EXHAUST FAN WILL BE REQUIRED 2001
 FMC 402.3.1.
  