Notes |
Date |
Text |
2006-04-28 00:00:00 | DENIED: | | 2ND REQUEST:PLEASE REVISE MANUAL J | | CALCULATIONS TO REFLECT THE EXISTING | | UNIT. PLANS INDICATE A 3 TON UNIT AND | | THE MANUAL J SHOWS A 2.2 TON. | | | | RETURN AIR REQUIRED FROM THE NEW STUDY | | ROOM. | | | | PROVISO: | | THE NEW BATHROOM SHALL HAVE A WINDOW | | WITH A MINIMUM OPENING OF 3 SQUARE FEET | | OR AN EXHAUST FAN WILL BE REQUIRED 2001 | | FMC 402.3.1. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|