| BUILDING PLAN REVIEW |
| *******DENIED******* |
| MYRON JACOBS(561) 805 6726 |
| E-MAIL:[email protected] |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| F.S.= FLORIDA (STATE) STATUTE |
| |
| 1) FBC 1606.2.5THE SYSTEM SELECTED |
| FROM THE SUBMITTED FLAT ROOF PRODUCT |
| APPROVAL NOA HAS A MAXIMUM DESIGN |
| PRESSURE OF LESS THAN -89 PSF AND CITES |
| GENERAL LIMITATION #9 (SEE PAGE 6 TO |
| 12).GENERAL LIMITATION #9 PROHIBITS |
| RATIONAL ANALYSIS OR EXTRAPOLATION TO |
| ENHANCE THE UPLIFT PRESSURE AT PERIMETER |
| AND CORNER AREAS BY REDUCING THE |
| FASTENER SPACING IN THESE AREAS.EITHER |
| SELECT AN ALTERNATIVE SYSTEM (OR PRODUCT |
| APPROVAL) THAT DOES NOT CITE GENERAL |
| LIMITATION #9.ALTERNATIVELY IF THE |
| SELECTED SYSTEM DOES CITE GENERAL |
| LIMITATION #9, IT MUST HAVE A MAXIMUM |
| DESIGN PRESSURE THAT EXCEEDS THE |
| PRESSURE IN ROOF ZONE 3 (TYPICALLY -89 |
| PSF FOR MEAN ROOF HEIGHT OF 30 FEET OR |
| LESS). THE SYSTEM SUBMITTED IS FOR A |
| POURRED GYPSUM CONCRETE DECK HOWEVER,THE |
| FLAT ROOF REFLECTS A WOOD DECK. |
| |
| 2) BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY. THE ACTUAL PERMIT |
| SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |
| PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| BUILDING PLAN REVIEW |
| MYRON JACOBS. |
| TEL: (561)805-6726 |
| FAX: (561)659-8026 |
| [email protected] |
| |
| |
| |
| |
| |