Date Text
2005-09-19 00:00:00DENIED
 SAME NOTES FROM FIRST REVIEW.
  
 3.SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR THE FOLLOWING.
 BUILT-UP ROOFING, SHINGLES, AND
 HARDI-BOARD PRODUCTS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4.SIGN OWNER/AGENT ON ENERGY CALCS.
  
 5. MASTER BEDROOM WINDOW SHALL COMPLY
 WITH FBC 1005.4.4 FOR EMERGENCY ESCAPE
 RESCUE OPENING SIZES.SHOW ON PLANS.
  
 SECOND REVIEW NOTES NOT ADDRESSED:
  
 A.CONTRACTOR LICENSE U-19578 IS A
 CARPENTRY LICENSE AND IS NOT A QUALIFIED
 LICENSE TO DO ROOM ADDITIONS.A CHANGE
 OF CONTRACTOR IS REQUIRED TO COMPLETE
 THE WORK SHOWN ON THE PLANS SUBMITTED.
  
  
 ANY QUESTIONS CALL ME.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672