2005-09-19 00:00:00PROVISO:
 RETURN AIR TO BEDROOM AREAS ARE NOT
 SIZED IN ACCORDANCE WITH 2001 FBC(M)
 601.4 EXCEPTION 1.THE RETURNS SHALL BE
 AS FOLLOWS:
 MASTER SUITE 18" RETURN REQUIRED
 GUEST BEDROOMS 12" RETURN REQUIRED.
  
 PLEASE PROVIDE REVISION REFLECTING
 PROPER RETURN AIR SIZES PRIOR TO
 INSPECTION.
  