Plan Review Notes For Permit 05051451 |
Permit Number |
05051451 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2005-08-12 00:00:00 | DENIED: | | 1.FIRST FLOOR PLAN DOES NOT INDICATE | | GRILLE SIZES. | | | | 2.SECOND FLOOR PLAN RETURN AIR | | REQUIRED FOR THE ROOMS SEPARATED BY A | | DOOR FROM THE CENTRAL RETURN.PLEASE | | REFERENCE 2001 FBC(M)601.4 EXCEPTION 1 | | THROUGH 3 FOR PROPER SIZING OF THE | | RETURN AIR. | | | | 3.AUXILIARY DRAIN PAN WITH OVERFLOW | | PROTECTION REQUIRED PER 2001 | | FBC(M)307.2.3. | | | | 4.PLEASE PROVIDE SIZING OF THE | | REFRIGERANT LINES INDICATED ON THE 1ST | | FLOOR PLAN SHEET. | | | | 5.PLEASE NOTE, CONDENSATE SHALL | | TERMINATE A MINIMUM OF 12" FROM THE | | BUILDING STRUCTURE PER 2001 FBC | | 1503.4.4. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|