Plan Review Notes For Permit 05051451 |
Permit Number |
05051451 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2005-09-15 00:00:00 | | | | | PROVISO | | ~~~~~~~ | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW PRIOR TO ROUGH ELECTRICAL | | INSPECTION. | | | | 1} A 150 AMP PANEL HAS BEEN ADDED SINCE | | THE LAST REVIEW. THE LOCATION OF THE | | PANEL (IN THE BATHROOM) IS IN VIOLATION | | OF 240.24(E). INDICATE THE ROUGH | | LOCATION ON REVISION. | | | | 2} PLEASE CORRECT THE LOAD CALCULATION | | TO INCLUDE THE EXISTING AND THE ADDED | | LOADS. | | | | 3} THE 400 AMP SERVICE NOW SHOWN | | REPLACING THE 200 AMP SERVICE SHOWN ON | | THE PRIOR REVIEW, MUST HAVE A 1/0 GEC | | PER 250.66. SEE NOTE ON PLAN. | | | | 4} PLEASE NOTE A RECEPTACLE MUST BE | | ADDED PER 210.52(A)(1) FOR SPACING. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | | | | | |
|