Plan Review Notes
Plan Review Notes For Permit 05051451
Permit Number 05051451
Review Stop E
Sequence Number 3
Notes
Date Text
2005-09-15 00:00:00 
  
 PROVISO
 ~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW PRIOR TO ROUGH ELECTRICAL
 INSPECTION.
  
 1} A 150 AMP PANEL HAS BEEN ADDED SINCE
 THE LAST REVIEW. THE LOCATION OF THE
 PANEL (IN THE BATHROOM) IS IN VIOLATION
 OF 240.24(E). INDICATE THE ROUGH
 LOCATION ON REVISION.
  
 2} PLEASE CORRECT THE LOAD CALCULATION
 TO INCLUDE THE EXISTING AND THE ADDED
 LOADS.
  
 3} THE 400 AMP SERVICE NOW SHOWN
 REPLACING THE 200 AMP SERVICE SHOWN ON
 THE PRIOR REVIEW, MUST HAVE A 1/0 GEC
 PER 250.66. SEE NOTE ON PLAN.
  
 4} PLEASE NOTE A RECEPTACLE MUST BE
 ADDED PER 210.52(A)(1) FOR SPACING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW