Plan Review Notes For Permit 05051451 |
Permit Number |
05051451 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-06-14 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | | | 1. SHT 2 OF 8 SANITARY RISER DIAGRAMS DO | | NOT REFLECT THE FLOOR PLAN, NOR DO THEY | | MEET CODE REQUIREMENTS. CORRECT THE | | FOLLOWING: | | 1ST FLOOR | | A. THE LAV IS NOT VENTED. SECTION | | 901.2.1. | | B. NO DOUBLE TRAPING. THE W/C HAS AN | | INTEGRAL TRAP. SECTION 1002.1. | | C. NO HORIZONTAL DRY VENTS (PAST | | SHOWER). SECTIONS 905.3 & 905.4. | | 2ND FLOOR | | A. NO HORIZONTAL DRY VENTS (PAST | | FIXTURE LABELED TUB LAV) SECTIONS 905.3 | | & 905.4. | | B. 10 FIXTURES ON SANT. RISER, BUT 11 | | FIXTURES ON FLOOR PLAN. SECTION 104.2.1. | | C. NO DOUBLE TRAPING. THE W/C'S HAVE | | INTEGRAL TRAPS. SECTION 1002.1. | | D. NO HORIZONTAL DRY VENTS. (PAST LAVS) | | SECTIONS 905.3 & 905.4. | | E. FIXTURES NOT LABELED CORRECTLY, AND | | NOT SHOWN IN THE LAYOUT OF THE FLOOR | | PLAN. SECTION 104.2.1. | | F. LAVS NOT VENTED. SECTION 901.2.1. | | G. EXPLAIN PIPING PAST LAST FIXTURE | | LABELED LAV ON THE LEFT SIDE OF THE | | BRANCH LINE, AND PAST LAST SET OF | | FIXTURES ON THE BRANCH LINE. SECTION | | 104.2.1. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] | | | | | | | | |
|