Date |
Text |
2006-02-16 00:00:00 | PAUL SCHMITZ |
| FBC2001 FUEL GAS CODEPLAN REVIEW |
| FBC 2001 PLUMBING CODEPLAN REVIEW |
| FBC 2001 FL ACESSIBILITY CODE PLAN |
| REVIEW |
| "DENIED" |
| "PREVIOUS COMMENTS NOT ADDRESSED" |
| |
| DENIED |
| 1.) SHT A-1,A-2 |
| ?104.2 DRAWINGS AND SPECIFICATIONS |
| ?104.2.1 REQUIREMENTS. AS REQUIRED BY |
| ?104.3.1.1 OF THE CODE, TWO OR |
| MORE COPIES OF SPECIFICATIONS, AND OF |
| DRAWINGS DRAWN TO SCALE WITH |
| SUFFICIENT CLARITY AND DETAIL TO |
| INDICATE THE NATURE AND CHARACTER OF THE |
| WORK, SHALL ACCOMPANY THE APPLICATION |
| FOR A PERMIT.SUCH DRAWINGS AND |
| SPECIFICATIONS SHALL CONTAIN |
| INFORMATION, IN THE FORM OF NOTES OR |
| OTHERWISE, AS TO THE QUALITY OF |
| MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| CONFORMITY WITH THE TECHNICAL CODES. |
| SUCH INFORMATION SHALL BE SPECIFIC, |
| AND THE TECHNICAL CODES SHALL NOT BE |
| CITED AS A WHOLE OR IN PART, NOR |
| SHALL THE TERM "LEGAL" OR ITS |
| EQUIVALENT BE USED AS A SUBSTITUTE FOR |
| SPECIFIC INFORMATION.ALL |
| INFORMATION, DRAWINGS, SPECIFICATIONS |
| AND |
| ACCOMPANYING DATA SHALL BEAR THE NAME |
| AND SIGNATURE OF THE PERSON |
| RESPONSIBLE FOR THE DESIGN. |
| 2.) |
| SECTION 11-4 |
| ACCESSIBLE ELEMENTS AND |
| SPACES:SCOPE AND TECHNICAL REQUIREMENTS |
| ?11-4.1 MINIMUM REQUIREMENTS. |
| ?11-4.1.1 APPLICATION. |
| ?11-4.1.1(1) GENERAL. THIS CODE |
| ESTABLISHES THE MINIMUM STANDARDS FOR |
| THE ACCESSIBILITY OF BUILDINGS AND |
| FACILITIES BUILT OR ALTERED WITHIN |
| THE STATE. |
| ?11-4.1.1(1)(A) ALL AREAS OF NEWLY |
| DESIGNED OR NEWLY CONSTRUCTED |
| BUILDINGS AND FACILITIES REQUIRED |
| TO BE ACCESSIBLE BY ?11-4.1.2 AND |
| ?11-4.1.3 AND ALTERED PORTIONS OF |
| EXISTING BUILDINGS AND FACILITIES |
| REQUIRED TO BE ACCESSIBLE BY |
| ?11-4.1.6 SHALL COMPLY WITH THIS CODE, |
| ?11-4.1 THROUGH ?11-4.35, UNLESS |
| OTHERWISE PROVIDED IN THIS |
| SECTION OR AS MODIFIED IN A |
| SPECIAL APPLICATION SECTION. |
| 3.) SHT P-1 |
| A)PROVIDE A DWV AND WATER PIPE |
| ISOMETRIC.SEC 104.2 |
| B) WATER HEATER DETAIL |
| ?P607.3 THERMAL EXPANSION CONTROL. A |
| MEANS OF CONTROLLING INCREASED |
| PRESSURE CAUSED BY THERMAL EXPANSION |
| SHALL BE PROVIDED WHERE REQUIRED IN |
| ACCORDANCE WITH ?P607.3.1 AND ?P607.3.2. |
| |
| END OF COMMENTS, QUESTIONS |