2005-12-03 00:00:00------------------DENIED----------------
  
 1) DUCT SIZES, GRILL DESIGNATION AND CFM
 MISSING IN SUITES 104 THRU 110 AND 204
 THRU 208. PLEASE INCLUDE ALL NECESSARY
 INFORMATION ON PLAN.
  
 2) KEY NOTES 5,6,7 ON PAGES M2 AND M3
 REFER TO DETAIL 1/M7 FOR DUCT/DIFFUSER
 SIZES AND LAYOUT. THIS DETAIL CONTAINS
 NO SUCH INFORMATION.
  
 3) KEY NOTES 5,6,7 ON PAGES M4 AND M5
 REFER TO DETAIL 1/M8 FOR DUCT/DIFFUSER
 SIZES AND LAYOUT. THIS DETAIL CONTAINS
 NO SUCH INFORMATION.
  
 4) VAV T1-14 ON PAGE M2 REFERENCES KEY
 NOTE 4 (FIRE DAMPER EXCEPTION). DUCT IS
 NOT SHOWN TO RUN THE MIN. 5' PAST THE
 RATED WALL TO MEET THE CONDITIONS OF THE
 FIRE DAMPER EXCEPTION.
  
 5) PAGE M5 SUITE 209 SHOWS A 24X18 DUCT
 FEEDING VAV T2-20 AND T2-21 EXCLUSIVELY.
 THE TWO VAVS COMBINED CALL FOR A TOTAL
 OF 270 CFM. IS THIS INTENTIONAL?
  
 6) GENERAL HVAC NOTE #9 CALLS FOR DUCT
 SMOKE DETECTORS IN ALL 4 AC SYSTEMS
 BASED ON CFMS.PLEASE INDICATE ON PLAN
 THE LOCATION OF DUCT SMOKE DETECTORS,
 ENSURING SERVICE/INSPECTION ACCESS AND
 COMPLIANCE WITH MANUFACTURER'S
 INSTALLATION INSTRUCTIONS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT
 RONALD J REGUEIRO AT 561.805.6734 OR
 PATTY KRAUS AT 561.805.6719