2005-12-03 00:00:00 | ------------------DENIED---------------- |
| |
| 1) DUCT SIZES, GRILL DESIGNATION AND CFM |
| MISSING IN SUITES 104 THRU 110 AND 204 |
| THRU 208. PLEASE INCLUDE ALL NECESSARY |
| INFORMATION ON PLAN. |
| |
| 2) KEY NOTES 5,6,7 ON PAGES M2 AND M3 |
| REFER TO DETAIL 1/M7 FOR DUCT/DIFFUSER |
| SIZES AND LAYOUT. THIS DETAIL CONTAINS |
| NO SUCH INFORMATION. |
| |
| 3) KEY NOTES 5,6,7 ON PAGES M4 AND M5 |
| REFER TO DETAIL 1/M8 FOR DUCT/DIFFUSER |
| SIZES AND LAYOUT. THIS DETAIL CONTAINS |
| NO SUCH INFORMATION. |
| |
| 4) VAV T1-14 ON PAGE M2 REFERENCES KEY |
| NOTE 4 (FIRE DAMPER EXCEPTION). DUCT IS |
| NOT SHOWN TO RUN THE MIN. 5' PAST THE |
| RATED WALL TO MEET THE CONDITIONS OF THE |
| FIRE DAMPER EXCEPTION. |
| |
| 5) PAGE M5 SUITE 209 SHOWS A 24X18 DUCT |
| FEEDING VAV T2-20 AND T2-21 EXCLUSIVELY. |
| THE TWO VAVS COMBINED CALL FOR A TOTAL |
| OF 270 CFM. IS THIS INTENTIONAL? |
| |
| 6) GENERAL HVAC NOTE #9 CALLS FOR DUCT |
| SMOKE DETECTORS IN ALL 4 AC SYSTEMS |
| BASED ON CFMS.PLEASE INDICATE ON PLAN |
| THE LOCATION OF DUCT SMOKE DETECTORS, |
| ENSURING SERVICE/INSPECTION ACCESS AND |
| COMPLIANCE WITH MANUFACTURER'S |
| INSTALLATION INSTRUCTIONS. |
| |