2006-02-08 00:00:00******* UNSAT **********
  
 1)NOTE: PLEASE SEE SOME NOTES FROM
 PREVIOUS REVIEW WHICH NEED TO BE
 ADDRESSED.
  
  
  
  
 1)NOTE: OK
  
 2)NOTE: OK
  
 3)NOTE:? THIS IS UNCLEAR, AS LIGHTING
 LOADS ON "AM" SCHEDULE DO NOT SEEM TO
 CORRELATE WITH CALCS SHOWN ONE-1
  
 **PLEASE SEE THAT ALL CONTINUOUS
 LOADS ARE SHOWN ON LOAD CALCULATIONS
 INCLUDING ANY LARGEST MOTOR LOADS AT
 125%.
 215.3,230.42 ETC.
 PLEASE SEE ONLY EXT LTS SEEM TO BE SHOWN
 AT 125%.
  
 4)NOTE: NO, ? SEE NOTE ABOVE AS, THE
 LOADS ON "AM" SHOULD BE THE SAME AS
 SHOWN FOR MAIN BLDG SERVICE?
 PLEASE VERIFY WHY THIS IS SHOWN
 SUBSTANTIALLY LARGER.
  
 **PLEASE CORRLELATE LOADS SHOWN ON
 MSB "AM" WITH RISER
 CALCULATIONS/LOAD(S).
 215.5
  
 5)NOTE: OK
  
 ** PLEASE CALL TO GO OVER COMMENTS AS
 SHEETS FOR INTERIOR WALLS ETC MAY BE
 STAMPED IF NEEDED FOR INSPECTIONS ONCE
 FIRE REVIEW IS DONE AND PASSED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATEIN CONTACTING
 THIS OFFICE.
  