Plan Review Notes For Permit 05051446 |
Permit Number |
05051446 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2006-02-08 00:00:00 | ******* UNSAT ********** | | | | 1)NOTE: PLEASE SEE SOME NOTES FROM | | PREVIOUS REVIEW WHICH NEED TO BE | | ADDRESSED. | | | | | | | | | | 1)NOTE: OK | | | | 2)NOTE: OK | | | | 3)NOTE:? THIS IS UNCLEAR, AS LIGHTING | | LOADS ON "AM" SCHEDULE DO NOT SEEM TO | | CORRELATE WITH CALCS SHOWN ONE-1 | | | | **PLEASE SEE THAT ALL CONTINUOUS | | LOADS ARE SHOWN ON LOAD CALCULATIONS | | INCLUDING ANY LARGEST MOTOR LOADS AT | | 125%. | | 215.3,230.42 ETC. | | PLEASE SEE ONLY EXT LTS SEEM TO BE SHOWN | | AT 125%. | | | | 4)NOTE: NO, ? SEE NOTE ABOVE AS, THE | | LOADS ON "AM" SHOULD BE THE SAME AS | | SHOWN FOR MAIN BLDG SERVICE? | | PLEASE VERIFY WHY THIS IS SHOWN | | SUBSTANTIALLY LARGER. | | | | **PLEASE CORRLELATE LOADS SHOWN ON | | MSB "AM" WITH RISER | | CALCULATIONS/LOAD(S). | | 215.5 | | | | 5)NOTE: OK | | | | ** PLEASE CALL TO GO OVER COMMENTS AS | | SHEETS FOR INTERIOR WALLS ETC MAY BE | | STAMPED IF NEEDED FOR INSPECTIONS ONCE | | FIRE REVIEW IS DONE AND PASSED. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATEIN CONTACTING | | THIS OFFICE. | | | | DEWEY PALMER' | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|