Plan Review Notes For Permit 05051446 |
Permit Number |
05051446 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-12-22 00:00:00 | ******DENIED****** | | | | 1) PLEASE PROVIDE FIRE RESISTANCE | | INFORMATION FOR NEW AWNINGS. | | | | 2) PLANS MENTION DUCT SMOKE DETECTORS. | | DEVICES WHERE INSTALLED SHALL INITIATE A | | GENERAL FIRE ALARM IN ACCORDANCE WITH | | LOCAL REQUIREMENTS, AND IF TIED INTO A | | FIRE ALARM SYSTEM. | | | | 3) ADDITIONAL EXIT SIGNS REQUIRED IN | | CORRIDORS TO SARTISFY MINIMUM 100' | | DISTANCE REQUIREMENT. | | | | 4) IF APPLICABLE, SEPARATE SHOP DRAWINGS | | AND PERMITS REQUIRED FOR FIRE SPRINKLER | | AND FIRE ALARM SYSTEMS. | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | FIRE PLAN REVIEW (561) 805-6722 |
|