Plan Review Notes For Permit 05051446 |
Permit Number |
05051446 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-12-20 00:00:00 | ***UNSAT *** | | | | 1)NOTE: PLEASE SEE DUE TO MAJOR INCREASE | | IN SCOPE OF WORK FROM ORIGINAL PERMIT | | APPLICATION AND PLANS SUBMITTED, PLEASE | | ADJUST VALUE FOR COMPLETE SCOPE OF WORK. | | 104.6.5 FBC, ADMINISTRATIVE CODE | | AMENDMENTS. | | | | 2)NOTE: PLEASE SEE MECHANICAL REVIEW | | COMMENTS SND POSSIBLE FIRE REVIEW | | COMMENTS WHICH WILL AFFECT ELECTRICAL | | PLANS. | | | | 3)NOTE: PLEASE SEE THAT ALL CONTINUOUS | | LOADS ARE SHOWN ON LOAD CALCULATIONS | | INCLUDING ANY LARGEST MOTOR LOADS AT | | 125%. | | 215.3,230.42 ETC. | | PLEASE SEE ONLY EXT LTS SEEM TO BE SHOWN | | AT 125%. | | | | 4)NOTE: PLEASE CORRLELATE LOADS SHOWN ON | | MSB "AM" WITH RISER | | CALCULATIONS/LOAD(S). | | 215.5 | | | | 5)NOTE: PLEASE VERIFY OF THE 1200 MCB IS | | BACKFED INTO PANEL. THIS APPEARS TO BE | | SHOWN ON THE PANEL SCHEDULE AS WELL AS | | BEING INDICATED ON THE TOP OF THE PANEL | | AS A MCB PANEL.?? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATEIN CONTACTING | | THIS OFFICE. | | | | DEWEY PALMER' | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|