2005-12-23 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 05051446 |
| ADD: 2247 PALM BEACH LAKES |
| CONT: ANDREA CONSTRUCTION |
| TEL: (561)358-4797 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) SINCE THE SCOPE OF WORK HAS CHANGED |
| UPDATE THE VALUE OF THE WORK TO BE |
| COMPLETED UNDER THIS PERMIT. |
| |
| 2) EXTERIOR AWNING IS TO BE COVERED |
| UNDER A SEPERATE PERMIT. |
| 104.1.1 WPB ADMINISTRATIVE CODE. |
| |
| 3) PLANS DO NOT INDICATE THE MINIMUM |
| BUILDING TYPE?601.2.1 |
| IF BUILDING IS FIRE SPRINKLERED? IF |
| SUPERVISED? TABLE 600 |
| |
| 4) SHEETS A1-A2 BOTH SHOW AN EXIT ACCESS |
| CORRIDOR BUT DOESN'T PROVIDE A UL |
| LISTING OR GYPSUM LISTING FOR THE WALL |
| ASSEMBLY OR FIRE RESISTANCE |
| RATING?704.2.4. |
| |
| 5)TABLE 803.3 MINIMUM INTERIOR FINISH |
| CLASSIFICATION; PROVIDE INFORMATION |
| BASED ON INTERIOR FINISH REQUIREMENTS |
| BASED ON OCCUPANCY |
| |
| 6) SUITE# 104 DOOR BY THE ELEVATOR |
| DOESN'T MEET REQUIREMENTS OF: |
| 11-4.13.6 MANEUVERING CLEARENCES |
| AT DOORS. MINIMUM MANEUVERING CLEARENCES |
| AT DOORS THAT ARE NOT AUTOMATIC OR |
| POWER-ASSISTED SHALL BE AS SHOWN IN |
| FIG. 25. THE FLOOR OR GROUND AREA WITH |
| IN THE REQUIRED CLEARENCES SHALL BE |
| CLEAR & LEVEL. |
| REQUIRES 18" OF WALL NEXT TO THE |
| LATCH PULL SIDE. |
| |
| 7) SCOPE OF WORK REVEALS THAT WINDOWS |
| ARE TO BE REPLACED: |
| PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| 1606.1.4(1) IN WIND BORNE DEBRIS |
| REGIONS, EXTERIOR GLAZING THAT RECEIVES |
| POSITIVE PRESSURE IN BUILDINGS SHALL BE |
| ASSUMED TO BE OPENINGS UNLESS SUCH |
| GLAZING IS IMPACT RESISTANT OR PROTECTED |
| WITH AN IMPACT RESISTANT COVERING MEET- |
| ING THE REQUIREMENTS OF SSTD 12, ASTM |
| E 1886 AND ASTM E 1996 OR MIAMI-DADE. |
| 1) GLAZED OPENINGS LOCATED WITHIN 30 FT |
| OF GRADE SHALL MEET THE REQUIREMENTS OF |
| LARGE MISSLE TEST. |
| FL BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORTS,MISSING REPORTS ARE AS |
| FOLLOWS: |
| REPLACEMENT WINDOWS . |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |