Plan Review Notes For Permit 05051446 |
Permit Number |
05051446 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-06-21 00:00:00 | BUILDING PROVISOS: | | | | 1)704.2.1.4 CORRIDOR PARTITIONS, SMOKE | | STOP PARTITIONS, HORIZONTAL EXIT PART- | | ITIONS, EXIT ENCLOSURES, AND FIRE | | RATED WALLS REQUIRED TO HAVE PROTECTED | | OPENINGS SHALL BE EFFECTIVELY AND | | PERMANETLY IDENTIFIED WITH SIGNS OR | | STENCILING IN A MANNER ACCEPTABLE TO THE | | AUTHORITY HAVING JURISDICTION. SUCH IDEN | | TIFICATION SHALL BE ABOVE ANY DECORATIVE | | CEILING CEILING AND IN CONCEALED SPACES. | | SUGGESTED WORDING" FIRE & SMOKE BARRIER | | PROTECT ALL OPENINGS". | | | | 2)705.7.1 JOINTS INSTALLED IN OR BE- | | TWEEN FIRE RESISTANT WALLS, FIRE RESIS- | | TANT FLOORS OR FLOOR/ CEILING ASSEMBLIES | | AND FIRE RESISTANT ROOFS OR ROOF/ CEIL- | | ING ASSEMBLIES SHALL BE PROTECTED BY AN | | APPROVED FIRE RESISTANT JOINT SYSTEM | | DESIGNED TO RESIST THE PASSAGE OF FIRE | | FOR A PERIOD NOT LESS THAN THE RE- | | QUIRED FIRE RESISTANCE RATING OF THE | | WALL, FLOOR OR FLOOR IN OR BETWEEN | | WHICH IT IS INSTALLED. | | BUILDING PLAN REVIEW | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 |
|