Plan Review Notes For Permit 05051429 |
Permit Number |
05051429 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-06-27 00:00:00 | | | PLEASE NOTE THE PREVIOUS NOTES REQUESTED | | INFORMATION ON LOCATION OF EQUIPMENT. | | THE TRANSFER SWITCH AND DISCONNECT | | REQUIRED BY 225.36 ARE NOT SHOWN. ALSO | | THERE IS NO INDICATION OF FEEDER ROUTING | | FROM THE GENERATOR TO THE DISCONNECT AND | | THEN TRANSFER SWITCH SINCE NO TRANSFER | | SWICH WAS LOCATED ON THE SITE PLAN. | | | | REGARDING THE 100 AMP PANEL SHOWN BEING | | FED FROM THE TRANSFER SWITCH. | | PLEASE SHOW LOCATION ON A SITE/FLOOR | | PLAN. INDICATE WHICH IS NEW AND WHICH IS | | EXISTING EQUIPMENT ON THE RISER. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|