Sequence Number 2
Notes
Date Text
2005-06-27 00:00:00 
 PLEASE NOTE THE PREVIOUS NOTES REQUESTED
 INFORMATION ON LOCATION OF EQUIPMENT.
 THE TRANSFER SWITCH AND DISCONNECT
 REQUIRED BY 225.36 ARE NOT SHOWN. ALSO
 THERE IS NO INDICATION OF FEEDER ROUTING
 FROM THE GENERATOR TO THE DISCONNECT AND
 THEN TRANSFER SWITCH SINCE NO TRANSFER
 SWICH WAS LOCATED ON THE SITE PLAN.
  
 REGARDING THE 100 AMP PANEL SHOWN BEING
 FED FROM THE TRANSFER SWITCH.
 PLEASE SHOW LOCATION ON A SITE/FLOOR
 PLAN. INDICATE WHICH IS NEW AND WHICH IS
 EXISTING EQUIPMENT ON THE RISER.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  