Plan Review Notes For Permit 05051429 |
Permit Number |
05051429 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-06-02 00:00:00 | | | PLEASE PROVIDE A SITE/FLOOR PLAN SHOWING | | THE PHYSICAL LOCATION OF THE SERVICE AND | | GENERATOR EQUIPMENT SO THAT DISCONNECT | | GROUPING AND COMPLIANCE WITH 225.31 & 32 | | CAN BE VERIFIED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|