2005-08-15 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT:05051382 |
| ADD: 249 ASHWORTH ST |
| CONT:ALL AMERICAN SHUTTERS |
| TEL: (561)712-9882 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVISION SHUTTERS: |
| ACTION: DENIED |
| |
| 1) A NOTIRIZED LETTER FROM THE HOME |
| OWNER STATING THAT THESE SHUTTERS ARE TO |
| BE USED ONLY FOR SECURITY. |
| |
| 2)THE FL COVERSHEET LIST ALL PRODUCT |
| APPROVALS LISTED BY STATE, PROVIDE THE |
| COVER SHEET FOR ACCORDIAN SHUTTERS WITH |
| THE CORRESPONDING DADE COUNTY REPORT. |
| |
| 3)1005.4.5 SECURITY AND HURRICANE |
| PROTECTION DEVICES. BARS, GRILLES, |
| GRATES OR SIMILAR SECURITY DEVICES |
| SHALL BE PERMITTED PROVIDED THE |
| MINIMUM SIZE AND OPERATIONAL |
| CONSTRAINTS OF SUCH DEVICES ARE IN |
| ACCORDANCE WITH 1005.4.2,?1005.4.3, AND |
| 1005.4.4.THE TEMPORARY |
| INSTALLATION OR CLOSURE OF STORM |
| SHUTTERS, PANELS, AND OTHER APPROVED |
| HURRICANE PROTECTION DEVICES SHALL BE |
| PERMITTED ON EMERGENCY ESCAPE AND |
| RESCUE OPENINGS IN GROUP R OCCUPANCIES |
| DURING THE THREAT OF A STORM. |
| SUCH DEVICES SHALL NOT BE REQUIRED TO |
| COMPLY WITH THE OPERATIONALCONSTRAINTS |
| OF 1005.4.2, 1005.4.3 AND?1005.4.4. |
| WHILE SUCH PROTECTION IS PROVIDED, AT |
| LEAST ONE MEANS OF ESCAPE FROM THE |
| DWELLING OR DWELLING UNIT SHALL BE |
| PROVIDED.THE MEANS OF ESCAPE SHALL BE |
| WITHIN THE FIRST FLOOR OF THE DWELLING |
| OR DWELLING UNIT AND SHALL NOT BE |
| LOCATED WITHIN AGARAGE.OCCUPANTS IN |
| ANY PART OF THE DWELLING OR DWELLING |
| UNIT SHALL BE ABLE TO ACCESS THE MEANS |
| OF ESCAPE WITHOUT PASSING THROUGH A |
| LOCKABLEDOOR NOT UNDER THEIR CONTROL. |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| |